LEP-D Comfort Control Model

VapaNet (LEP-D) pulsed energy control is also used in precision tolerant applications.
 
Features
• 7 different capacities between 5-90 kg/h
• Pulsed energy control 8-100%
• Controllable with all analog DC signals and potentiometric signal
• Electric supply options; 200-440 volts, Phase+Notr or 2 phase, 3 phase
• Digital Operation Display
• Ability to communicate with BMS systems
• BAbility to send a run/fail signal to the BMS system
• Up to 10 units interconnected and controlled as a single system
• Foam protection
• Stainless steel drain pan
• Drain Pump
• Control Features
 
The humidifier can be controlled by a Vapac or other brand sensor installed in the duct or room, or by a signal from outside.
 
Room Distribution Unit (RDU)
Suitable for LE-D and LEP-D models up to 45 kg/h capacity for duct or non-switchboard applications. It can be used both humidifier-mounted and independently mounted directly in the room.
 
Optional Accessories
• Alpha Numeric display
• Connection cable

GET AN OFFER
Technical Details
 Capacity, Electric İnformation, Dimensions and Weight
                 
 On/Off and Proportional Control (%20-100)
Code   40112205 40112209 40112218 40112230 40112245 40112260 40112290
Model   LE05PD LE09PD LE18PD LE30PD LE45PD LE60PD LE90PD
Max. Steam Output kg/h 0.4-5 0.72-9 43221 11050 16591 22132 32911
Number of cylinders             2 2
Diameter of Steam mm 35 35 35 54 54 54 54
Voltage V 200/440 380/440          
Electricity supply   Faz+N ya da 2 Faz 3 Faz          
Mak. Electric Power kW 45872 45875 45821 45799 34 45 67.8
Full load current (for each phase) Amper 45231 19/41 22/47 36/78 53/62 72/82 106/124
Max. fuse value (for each phase) Amper 32/16 63/25 50/32 100/50 80 2x50 2x80
Height mm 676 676 676 810 810 810 810
Width mm 430 430 430 520 520 990 990
Depth mm 320 320 320 415 415 415 415
Dry Weight  kg 34 36 39 40 40 74 75
Wet Weight  kg 48 50 66 67 67 127 128

 

Operating limits   Water Supply
Ambient temperature 5 - 35 °C   Conductivity 80-1000 µS
Water temperature 1° to 30°C   PH 7.3 - 8.0
Duct pressure -600 -2000Pa   Silica 0
      Water Pressure 1 - 8 Bar
      Hardness 50-500ppm