The High-Pressure Booster Min Is a high-pressure humidification unit without reverse osmosis unit. The unit has its own control unit, therefore it can operate stand alone, if required, the unit can also be connected to a Building Management System to control it. Standard version is MIN type. The capacity range is 60 Lt/h, and 800 Lt/h. Pumps can be mounted on stainless steel surface. One control unit, status display and operating hour counter can mount on a unit directly.
Frequency Control
Cumulus high pressure pumps are not modulated by frequency control. The reason is that the high-pressure pumps are designed for constant rotation. In this way, the pressure in the nozzle is always high enough to provide very fine water particles. Frequency-controlled applications cannot perform these fine water particles at low speeds.
In addition to the negative effect on atomization, frequency control reduces ins lifespan of the pump
Technical Specifications
| HP BOOSTER MIN 120 |
HP BOOSTER MIN 120 |
HP BOOSTER MIN 220 |
HP BOOSTER MIN 280 | HP BOOSTER MIN 480 | |
|
Maximum Pump Capacity (I/h) |
120 | 220 | 280 | 380 | 480 |
|
Dimensions (LxHxW) mm |
400x680x1110 | ||||
|
Weight (kg) |
65 | 70 | 75 | 80 | 85 |
|
Water conductivity (μS) |
5-20 | ||||
|
Operating pressure (bar) |
70-100 | ||||
|
Power consumption (kW) |
0,7 | 1,3 | 1,6 | 1,7 | 1,8 |
|
Control signal |
0-10v-4-20 m A | ||||
|
Ability to connect to the Air Handling Unit |
Yes | ||||
|
Standalone operation |
Yes | ||||
|
Maximum amount of zones |
12 | ||||
|
Water fresh safety |
Yes | ||||
|
Automatic restart when power is cut off |
Yes | ||||
|
External warning signal |
Optional | ||||
|
Maintenance signal |
Yes | ||||
|
Remote monitoring monitor |
Optional | ||||
|
Water pressure safety |
Yes | ||||
|
Overload protection |
Yes | ||||
|
Dynamic water pressure (bar) |
3 | ||||
|
Min./Max. temperature °C |
0-40°C | ||||
|
Power connection |
400V AC | ||||