Fibersox
GET AN OFFER
Fibersox™ series is produced from class A fireproof fabric with the best flame resistance feature, offering an 8-year warranty. It is used for environments that require heating, ventilation and light cooling that require absolute flame resistance
Technical Details
Property | Items | Index | Results | Code Compliance | Testing Organization | Remarks | |
Material Properties | Fire Safety | A2 | FIGRA, w/h ≤ 120 | 5 | GB 8624-2012 | NFTC | Formal Testing |
THR600s, MJ ≤ 7.5 | 0.9 | ||||||
Thermal value, MJ ≤ 3.0 | 11.6 | ||||||
S1 | SMOGRA, m²/s² s 30 | 20 | |||||
T5P600s, m² s 50 | |||||||
d0 | Flammable particles or droplet 600s | Compatible | |||||
t0 | Smoke toxicity ZAI | ZA1 | |||||
Class A2 | SMOGRA, m²/s² ≤ S30 | 9.May | EN13501-1:Al: 2009 | Formal Testing |
|||
T5P600s, m² ≤ 50 | 11.7 | 5GS | |||||
Flammable particle or droplet 600s | No | ||||||
Class A1 | Fire propagation index | 0.4 | BS 476-6:Al: 2009 | TUV SUD PSB | Formal Testing |
||
Weight | 300 g/m² ± 5% | 305 g | ASTM D3776 | ||||
System Performance | Resistance to Pressure | At 2000 Pa static pressure, no change in appearance, no flow, no damage | No change | JGJ141-2004 | National Ventilation Equipment Quality Supervision, Inspection and Testing Center | ||
Passive Permability | Passive permeability at a pressure of 500 Pa | ≤ 50 m²/h/m² | 15 m³/h/m² | ||||
Passive permeability at 1000 Pa pressure | ≤ 100 m²/h/m² | 30 m³/h/m² | |||||
Dimension Tolerance | ≤ 1 % | No change |